欧美日韩精品一区二区三区视频 _国产精品亚洲一区_久久久久看片_国产欧美日韩

Brass electric three-way valve

Products > Copper valve > Brass electric three-way valve

Brass electric three-way valve

Model: VA-7010
Nominal diameter: DN15 ~ 25mm
Nominal pressure: 1.6MPa
Ambient temperature: 0 ℃ -60 ℃
Medium: cold water, hot water
Medium temperature: 2 ℃ -95 ℃
Contact purchase
shared:

Electric three-way valve Overview
VA-7010 series fan coil electric valve for fan coil water flow control. Body forged brass, the drive using hysteresis synchronous motor as the driving force. Power open the valve, reset by the spring after the power is off (that is, the body off after power off), and with a manual valve operating mechanism is the central air conditioning system is one of the most widely used electric valve.


Electric three-way valve Specifications
◆ Drive motor: Hysteresis synchronous motor 
◆ Drive voltage: 220VAC, 50Hz / 60Hz (with AC24V, 110V to choose from) 
◆ Power consumption: ≤ 7.5VA 
◆ Body pressure: 1.6MPa 
◆ Allow Pressure difference: ≤0.13MPa 
◆ Suitable medium: cold water, hot water 
◆ Applicable medium temperature: 2 ℃ -95 ℃ 
◆ Applicable ambient temperature: 0 ℃ -60 ℃ 
◆ Opening and closing time: about 10 seconds, about 5 seconds off 
◆ Valve Body connection: ZG pipe thread (can also be customized according to user needs) 
◆ travel (theoretical): 4.0mm


Electric three-way valve The main material
◆ Body: brass (forging) 
◆ stem: 304 stainless steel 
◆ Sealing material: special rubber 
◆ Drive Chassis: Die Cast Aluminum 
◆ Drive Cover: Flame retardant ABS plastic

 

Electric three-way valve installation and commissioning
◆ Before installation must read the instructions, cut off the power and must be installed by professionals. 
◆ The flow direction must be the same as the direction of the arrow on the valve body. 
◆ The valve body must be above the fan water tray to ensure that dripping water will fall into the water receiving tray. 
◆ The valve body and driver must be installed within ± 60 ° in the vertical direction. At least 30mm above the space should be used for disassembly and assembly. The surrounding piping, equipment and buildings must maintain sufficient space for maintenance and repair, and must be installed in the maintenance personnel Through the access hole can reach places. 
◆ two and more than two electric valve can not be parallel, if you really need to use relays parallel isolation. 
◆ After installing the valve body and passing the pressure test to the pipeline, install the drive. 
◆ If the driver has been installed on the valve body, the driver must not be used during installation and commissioning as this may damage the driver. 
◆ The drive can not be wrapped with insulation material, otherwise it will affect its heat dissipation. 
◆ The driver must be reliably grounded through a wire of not less than 1.5mm2. The other wires should comply with the relevant standards of the electrician. 
◆ Installation is complete and check the correct, water-free power debugging. At least observe the three full drive cycles and make sure all components are correct and correct. 
◆ after passing through the anhydrous test, and then through the water debugging. System pressure on the water must be strictly controlled within 0.13MPa, in order to ensure the effectiveness of the electric valve on the water flow switch.


Electric three-way valve model comparison table

namemodelCaliber parametersABCThe maximum allowable pressurekv
Electric two-way valve ZLVA-7010-2151/2 "DN1555171030.13 MPa2.0
ZLVA-7010-2203/4 "DN2063171030.13 MPa2.5
ZLVA-7010-2251"DN25712251070.08 MPa3.8
Electric three-way valve ZLVA-7010-3151/2 "DN1555291030.13 MPa2.0
ZLVA-7010-3203/4 "DN2063291030.13 MPa2.5
ZLVA-7010-3251"DN2571381070.08 Mpa3.8



主站蜘蛛池模板: 图片| 苗栗市| 龙川县| 隆回县| 镇坪县| 遂川县| 湄潭县| 桃园市| 怀宁县| 正定县| 万年县| 巩留县| 潞西市| 招远市| 奉节县| 库尔勒市| 苍南县| 岳池县| 泾川县| 闸北区| 新余市| 夏邑县| 汝州市| 萨迦县| 比如县| 崇信县| 潼关县| 醴陵市| 松江区| 同仁县| 北安市| 广平县| 运城市| 云南省| 七台河市| 邻水| 夏河县| 紫云| 崇明县| 即墨市| 金乡县|